Differences between revisions 1 and 16 (spanning 15 versions)
Revision 1 as of 2019-12-08 15:35:39
Size: 1231
Comment:
Revision 16 as of 2019-12-13 14:02:56
Size: 4192
Comment:
Deletions are marked like this. Additions are marked like this.
Line 4: Line 4:

 1. Copy the corresponding template files from

  /kagra/Dropbox/Subsystems/VIS/TypeBData/SRM/OPLEV/templates/

 The templates are different for each suspension, therefore make sure you use the appropriate directory
  . /kagra/Dropbox/Subsystems/VIS/TypeBData/SRM/OPLEV/measurements/20191208/
 1. Into the newly created directory copy the corresponding template files from
  . /kagra/Dropbox/Subsystems/VIS/TypeBData/SRM/OPLEV/templates/. The templates are different for each suspension so make sure you use the correct ones.
Line 13: Line 9:
  * Align the oplev beam to the centre of the QPDs. Use the IM test channels to move the marionette such that the readout of the oplev in Normalized Displacement Units (ndu) are close to zero.
 1. Use diaggui to open the file SRM_TM_OPLEV_L_PREDIAG.xml, execute it, wait until it finishes and then save the results. Mind the name, it follows the suspension.
 1. Use diaggui to open the file SRM_TM_OPLEV_P_PREDIAG.xml, execute it, wait until it finishes and then save the results. Mind the name, it follows the suspension.
 1. Use diaggui to open the file SRM_TM_OPLEV_Y_PREDIAG.xml, execute it, wait until it finishes and then save the results. Mind the name, it follows the suspension.
  * Align the oplev beam to the centre of the QPDs. Use the IM test channels to move the marionette such that the readout of the oplev in Normalized Displacement Units (ndu) are close to zero. (Which medm screen shows this?)
 1. Use diaggui to open the file '''SRM_TM_OPLEV_L_PREDIAG.xml''', carry out the measurement and save the results.
 1. Use diaggui to open the file '''SRM_TM_OPLEV_P_PREDIAG.xml''', carry out the measurement and save the results.
 1. Use diaggui to open the file '''SRM_TM_OPLEV_Y_PREDIAG.xml''', carry out the measurement and save the results.
 1. Open the file '''SRM_TM_OPLEV_L_PREDIAG.xml''' again. At the TM-L resonant frequency '''around 0.656 Hz'''
  * Take a note of the amplitudes '''x_len''' and '''y_len''' in the plot '''"ADS: x_len (red), y_len (blue)"''' using the cursor feature of diaggui,
  * Take a note of the relative phase between '''x_len''' and '''y_len''' in the plot '''"Transfer function: x_len and y_len relative phase"'''.
   * If the phase is around 0° set x_len > 0 and y_len > 0.
   * If the phase is around ±180° set x_len > 0 and y_len < 0.
  * Take a note of the amplitudes '''x_tilt '''and '''y_tilt''' in the plot '''"ADS: x_tilt (red), y_tilt (blue)"'''.
  * Take a note of the relative phase between '''x_len''' and '''x_tilt''' in the plot "XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX".
   * If the phase is around 0° set x_tilt > 0.
   * If the phase is around ±180° set x_tilt < 0.
  * Take a note of the relative phase between '''x_len''' and '''y_tilt''' in the plot '''"XXXXXXXXXXXX"'''.
 1. Open the file '''SRM_TM_OPLEV_P_PREDIAG.xml'''. At the TM-P resonant frequency '''around 0.820 Hz'''
  * Take a note of the amplitudes '''x_len''' and '''y_len''' in the plot '''"ADS: x_len (red), y_len (blue)"''' using the cursor feature
  * Take a note of the relative phase between '''x_len''' and '''y_len'''; use the plot '''"Transfer function: x_len and y_len relative phase"'''; HOW TO USE THIS INFORMATION CORRECTLY?
  * Take a note of the amplitudes '''x_tilt '''and '''y_tilt''' in the plot '''"ADS: x_tilt (red), y_tilt (blue)"'''.
  * Take a note of the relative phase between '''x_tilt''' and '''y_tilt'''; use the plot '''"Transfer function: x_tilt and y_tilt relative phase"'''; HOW TO USE THIS INFORMATION CORRECTLY?
 1. Open the file '''SRM_TM_OPLEV_Y_PREDIAG.xml'''. At the TM-P resonant frequency '''around 1 Hz'''
  * Take a note of the amplitudes '''x_len''' and '''y_len''' in the plot '''"ADS: x_len (red), y_len (blue)"''' using the cursor feature,
  * Take a note of the relative phase between '''x_len''' and '''y_len'''; use the plot '''"Transfer function: x_len and y_len relative phase"'''; HOW TO USE THIS INFORMATION CORRECTLY?
  * Take a note of the amplitudes '''x_tilt '''and '''y_tilt''' in the plot '''"ADS: x_tilt (red), y_tilt (blue)"'''.
  * Take a note of the relative phase between '''x_tilt''' and '''y_tilt'''; use the plot '''"Transfer function: x_tilt and y_tilt relative phase"'''; HOW TO USE THIS INFORMATION CORRECTLY?
 1. Open the Matlab file oplev_diagonalization.m
 1. Scroll down to around line 104 and make sure the right-hand side of the five listed assignments refer to the suspension you are working with (BS, SR2, SR3, SRM).
 1. Scroll down to around line 133 and write the information in the section according to the examples, which are commented lines. '''How to write the signs correctly?'''
 1. Execute the file. Copy the matrix into the medm screen.
 1. Run diagnosis
 1. Write a klog with the following format.

Describe KAGRA/Subgroups/VIS/OpsManual/OpLev/TypeB here.

  1. In the corresponding directory for the suspension you are working with, create a new directory with the date as a name. For example,
    • /kagra/Dropbox/Subsystems/VIS/TypeBData/SRM/OPLEV/measurements/20191208/
  2. Into the newly created directory copy the corresponding template files from
    • /kagra/Dropbox/Subsystems/VIS/TypeBData/SRM/OPLEV/templates/. The templates are different for each suspension so make sure you use the correct ones.
  3. Align the optic into a convenient orientation.
    • Use Guardian to set the suspension in IM_DAMP mode.
    • Align the oplev beam to the centre of the QPDs. Use the IM test channels to move the marionette such that the readout of the oplev in Normalized Displacement Units (ndu) are close to zero. (Which medm screen shows this?)
  4. Use diaggui to open the file SRM_TM_OPLEV_L_PREDIAG.xml, carry out the measurement and save the results.

  5. Use diaggui to open the file SRM_TM_OPLEV_P_PREDIAG.xml, carry out the measurement and save the results.

  6. Use diaggui to open the file SRM_TM_OPLEV_Y_PREDIAG.xml, carry out the measurement and save the results.

  7. Open the file SRM_TM_OPLEV_L_PREDIAG.xml again. At the TM-L resonant frequency around 0.656 Hz

    • Take a note of the amplitudes x_len and y_len in the plot "ADS: x_len (red), y_len (blue)" using the cursor feature of diaggui,

    • Take a note of the relative phase between x_len and y_len in the plot "Transfer function: x_len and y_len relative phase".

      • If the phase is around 0° set x_len > 0 and y_len > 0.

      • If the phase is around ±180° set x_len > 0 and y_len < 0.

    • Take a note of the amplitudes x_tilt and y_tilt in the plot "ADS: x_tilt (red), y_tilt (blue)".

    • Take a note of the relative phase between x_len and x_tilt in the plot "XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX".

      • If the phase is around 0° set x_tilt > 0.

      • If the phase is around ±180° set x_tilt < 0.

    • Take a note of the relative phase between x_len and y_tilt in the plot "XXXXXXXXXXXX".

  8. Open the file SRM_TM_OPLEV_P_PREDIAG.xml. At the TM-P resonant frequency around 0.820 Hz

    • Take a note of the amplitudes x_len and y_len in the plot "ADS: x_len (red), y_len (blue)" using the cursor feature

    • Take a note of the relative phase between x_len and y_len; use the plot "Transfer function: x_len and y_len relative phase"; HOW TO USE THIS INFORMATION CORRECTLY?

    • Take a note of the amplitudes x_tilt and y_tilt in the plot "ADS: x_tilt (red), y_tilt (blue)".

    • Take a note of the relative phase between x_tilt and y_tilt; use the plot "Transfer function: x_tilt and y_tilt relative phase"; HOW TO USE THIS INFORMATION CORRECTLY?

  9. Open the file SRM_TM_OPLEV_Y_PREDIAG.xml. At the TM-P resonant frequency around 1 Hz

    • Take a note of the amplitudes x_len and y_len in the plot "ADS: x_len (red), y_len (blue)" using the cursor feature,

    • Take a note of the relative phase between x_len and y_len; use the plot "Transfer function: x_len and y_len relative phase"; HOW TO USE THIS INFORMATION CORRECTLY?

    • Take a note of the amplitudes x_tilt and y_tilt in the plot "ADS: x_tilt (red), y_tilt (blue)".

    • Take a note of the relative phase between x_tilt and y_tilt; use the plot "Transfer function: x_tilt and y_tilt relative phase"; HOW TO USE THIS INFORMATION CORRECTLY?

  10. Open the Matlab file oplev_diagonalization.m
  11. Scroll down to around line 104 and make sure the right-hand side of the five listed assignments refer to the suspension you are working with (BS, SR2, SR3, SRM).
  12. Scroll down to around line 133 and write the information in the section according to the examples, which are commented lines. How to write the signs correctly?

  13. Execute the file. Copy the matrix into the medm screen.
  14. Run diagnosis
  15. Write a klog with the following format.