Quiet mode uses only one cooler. Please follow (a) or (b), not (a) and (b). Obviously, the temp setting of a cooler that will be operated should be 22.5 or 22.56. | |
Line 5: | Line 6: |
(1)Quiet Mode (a) #1 cooler operation mode Close two doors (door btw outside and sound proof room and door btw pre-room and clean room). Operate #1(1st) cooler at 22.5C Open fully the air flow adjuster. Stop #2(2nd) cooler Close its air flow adjuster. Stop KOACHs 2 minute after the coolers operation. (b) #2 cooler operation mode Close two doors (door btw outside and sound proof room and door btw pre-room and clean room) Operate #2(2nd) cooler at 22.56C Open fully its air flow adjuster. Stop #1(1st) cooler Close its air flow adjuster. Stop KOACHs 2 minute after the coolers operation. |
Working mode uses both two coolers. |
Line 29: | Line 9: |
(2)Working mode | 1. '''[[http://klog.icrr.u-tokyo.ac.jp/osl/?r=11812|Quiet Mode]]''' a. #1 cooler operation mode |
Line 31: | Line 12: |
Operate both coolers at "23.8C" with fully opening the air adjusters. Operate KOACHs. Open two doors (door btw outside and sound proof room and door btw pre-room and clean room) of the PSL room with 10cm space. |
*Close two doors (door btw outside and sound proof room and door btw pre-room and clean room). *Operate #1(1st) cooler at 22.5C *Open fully the air flow adjuster. |
Line 35: | Line 16: |
The attached graph shows each temp during working mode. "Booth_PSL temp(set inside the clean area)" keeps almost same temp with that before action with short time disturbance. | *Stop #2(2nd) cooler *Close its air flow adjuster. |
Line 37: | Line 19: |
*Stop KOACHs 2 minute after the coolers operation. * #2 cooler operation mode *Close two doors (door btw outside and sound proof room and door btw pre-room and clean room) *Operate #2(2nd) cooler at 22.56C *Open fully its air flow adjuster. *Stop #1(1st) cooler *Close its air flow adjuster. *Stop KOACHs 2 minute after the coolers operation. * '''[[http://klog.icrr.u-tokyo.ac.jp/osl/?r=11812|Working mode]]''' *Operate both coolers at "23.8C" with fully opening the air adjusters. * Operate KOACHs. *Open two doors (door btw outside and sound proof room and door btw pre-room and clean room) of the PSL room with 10cm space. *The attached graph shows each temp during working mode. "Booth_PSL temp(set inside the clean area)" keeps almost same temp with that before action with short time disturbance. |
If your working time in the PSL room is over 30 min/ N(working people number) -> working mode, else, quiet mode.
Quiet mode uses only one cooler. Please follow (a) or (b), not (a) and (b). Obviously, the temp setting of a cooler that will be operated should be 22.5 or 22.56.
Working mode uses both two coolers.
- #1 cooler operation mode
- Close two doors (door btw outside and sound proof room and door btw pre-room and clean room).
- Operate #1(1st) cooler at 22.5C
- Open fully the air flow adjuster.
- Stop #2(2nd) cooler
- Close its air flow adjuster.
- Stop KOACHs 2 minute after the coolers operation.
- #2 cooler operation mode
- Close two doors (door btw outside and sound proof room and door btw pre-room and clean room)
- Operate #2(2nd) cooler at 22.56C
- Open fully its air flow adjuster.
- Stop #1(1st) cooler
- Close its air flow adjuster.
- Stop KOACHs 2 minute after the coolers operation.
- #1 cooler operation mode
- Operate both coolers at "23.8C" with fully opening the air adjusters.
- Operate KOACHs.
- Open two doors (door btw outside and sound proof room and door btw pre-room and clean room) of the PSL room with 10cm space.
- The attached graph shows each temp during working mode. "Booth_PSL temp(set inside the clean area)" keeps almost same temp with that before action with short time disturbance.
(The air adjuster is situated at the bottom of a duct of the precision cooler. You can slide a metal plate by hand.)