Close two doors (door btw outside and sound proof room and door btw pre-room and clean room). Operate #1(1st) cooler at 22.5C Open fully the air flow adjuster. |
*Close two doors (door btw outside and sound proof room and door btw pre-room and clean room). *Operate #1(1st) cooler at 22.5C *Open fully the air flow adjuster. |
Line 12: | Line 12: |
Stop #2(2nd) cooler Close its air flow adjuster. |
*Stop #2(2nd) cooler *Close its air flow adjuster. |
Line 15: | Line 15: |
Stop KOACHs 2 minute after the coolers operation. | *Stop KOACHs 2 minute after the coolers operation. |
Line 19: | Line 19: |
Close two doors (door btw outside and sound proof room and door btw pre-room and clean room) Operate #2(2nd) cooler at 22.56C Open fully its air flow adjuster. |
*Close two doors (door btw outside and sound proof room and door btw pre-room and clean room) *Operate #2(2nd) cooler at 22.56C *Open fully its air flow adjuster. |
Line 23: | Line 23: |
Stop #1(1st) cooler Close its air flow adjuster. |
*Stop #1(1st) cooler *Close its air flow adjuster. |
Line 26: | Line 26: |
Stop KOACHs 2 minute after the coolers operation. | *Stop KOACHs 2 minute after the coolers operation. |
Line 31: | Line 31: |
Operate both coolers at "23.8C" with fully opening the air adjusters. Operate KOACHs. Open two doors (door btw outside and sound proof room and door btw pre-room and clean room) of the PSL room with 10cm space. |
*Operate both coolers at "23.8C" with fully opening the air adjusters. * Operate KOACHs. *Open two doors (door btw outside and sound proof room and door btw pre-room and clean room) of the PSL room with 10cm space. |
Line 35: | Line 35: |
The attached graph shows each temp during working mode. "Booth_PSL temp(set inside the clean area)" keeps almost same temp with that before action with short time disturbance. | *The attached graph shows each temp during working mode. "Booth_PSL temp(set inside the clean area)" keeps almost same temp with that before action with short time disturbance. |
If your working time in the PSL room is over 30 min/ N(working people number) -> working mode, else, quiet mode.
(1)Quiet Mode
- #1 cooler operation mode
- Close two doors (door btw outside and sound proof room and door btw pre-room and clean room).
- Operate #1(1st) cooler at 22.5C
- Open fully the air flow adjuster.
- Stop #2(2nd) cooler
- Close its air flow adjuster.
- Stop KOACHs 2 minute after the coolers operation.
- #2 cooler operation mode
- Close two doors (door btw outside and sound proof room and door btw pre-room and clean room)
- Operate #2(2nd) cooler at 22.56C
- Open fully its air flow adjuster.
- Stop #1(1st) cooler
- Close its air flow adjuster.
- Stop KOACHs 2 minute after the coolers operation.
- #1 cooler operation mode
Working mode
- Operate both coolers at "23.8C" with fully opening the air adjusters.
- Operate KOACHs.
- Open two doors (door btw outside and sound proof room and door btw pre-room and clean room) of the PSL room with 10cm space.
- The attached graph shows each temp during working mode. "Booth_PSL temp(set inside the clean area)" keeps almost same temp with that before action with short time disturbance.
(The air adjuster is situated at the bottom of a duct of the precision cooler. You can slide a metal plate by hand.)