Size: 1654
Comment:
|
← Revision 10 as of 2019-12-06 07:44:56 ⇥
Size: 1656
Comment:
|
Deletions are marked like this. | Additions are marked like this. |
Line 5: | Line 5: |
If your working time in the PSL room is over 30 min/ N(working people number) -> working mode, else, quiet mode.
Quiet mode uses only one cooler. Please follow (a) or (b), not (a) and (b). Obviously, the temp setting of a cooler that will be operated should be 22.5 or 22.56.
Working mode uses both two coolers.
- #1 cooler operation mode
- Close two doors (door btw outside and sound proof room and door btw pre-room and clean room).
- Operate #1(1st) cooler at 22.5C
- Open fully the air flow adjuster.
- Stop #2(2nd) cooler
- Close its air flow adjuster.
- Stop KOACHs 2 minute after the coolers operation.
- #2 cooler operation mode
- Close two doors (door btw outside and sound proof room and door btw pre-room and clean room)
- Operate #2(2nd) cooler at 22.56C
- Open fully its air flow adjuster.
- Stop #1(1st) cooler
- Close its air flow adjuster.
- Stop KOACHs 2 minute after the coolers operation.
- #1 cooler operation mode
- Operate both coolers at "23.8C" with fully opening the air adjusters.
- Operate KOACHs.
- Open two doors (door btw outside and sound proof room and door btw pre-room and clean room) of the PSL room with 10cm space.
- The attached graph shows each temp during working mode. "Booth_PSL temp(set inside the clean area)" keeps almost same temp with that before action with short time disturbance.
(The air adjuster is situated at the bottom of a duct of the precision cooler. You can slide a metal plate by hand.)