Line 36: Line 36:

cry_comp.dbに
record (ai, "$(SYSTEM):Comp:Ch8")
{
    field (DESC, "D3775:Compressor ch8 value" )
    field (DTYP, "devFromArray")
    field (INP, "$(SYSTEM):D3640-D4599 @ 135" )
    field (SCAN,"$(SCAN) second")
}
record (ai, "K1:PEM-BLAB_KIKI_BARO")
{
    field (DESC, "D3776:Barometer value" )
    field (DTYP, "devFromArray")
    field (INP, "$(SYSTEM):D3640-D4599 @ 136" )
    field (SCAN,"$(SCAN) second")
}
record (ai, "K1:PEM-BLAB_KIKI_TEMP")
{
    field (DESC, "D3777:Thermometer value" )
    field (DTYP, "devFromArray")
    field (INP, "$(SYSTEM):D3640-D4599 @ 137" )
    field (SCAN,"$(SCAN) second")
}
record (ai, "K1:PEM-BLAB_KIKI_HUMI")
{
    field (DESC, "D3778:Hygrometer value" )
    field (DTYP, "devFromArray")
    field (INP, "$(SYSTEM):D3640-D4599 @ 138" )
    field (SCAN,"$(SCAN) second")
}

のように加えた後、IOCを立ち上げ直したが、反映されていない模様。
可能性としては、/home/kagra以下のdbに入れたから?/home/controls以下のdbに入れたから?2つはシンボリックリンクだが、反映されないことがある。←チェックする必要あり。

参考

  • JGW-T1503712

    • 日立造船による機器制御についての仕様書。
  • JGW-T1503713

    • 機器制御にあるPLCにIOCを設定するメモ。EPICSトランスレータと呼んでいて,EPICSにデータを流すためのもの。
  • JGW-E1604970

    • 機器制御用のCDS計算機(k1kiki0)でIOCを設定するメモ。
    • k1kiki0はトランスレータがあるので必要ない気がする。。?

ネットワーク

項目

IP アドレス

EPICSトランスレータ

---

k1kiki0

10.68.10.139

温湿度気圧計接続テスト

JGW-T1503712中のドキュメント01 p23によると、CCL18、CCL19は予備となっており、使われていない。そこで、CCL18のch1,2,3を用いて接続テストを行う。Source--/base-3.14.12.2/db/cry_comp.dbによると、

record (ai, "$(SYSTEM):Comp:Ch8") {

  • field (DESC, "D3775:Compressor ch8 value" ) field (DTYP, "devFromArray") field (INP, "$(SYSTEM):D3640-D4599 @ 135" ) field (SCAN,"$(SCAN) second")

} record (ai, "$(SYSTEM):XEND:Cryo:Ch1") {

  • field (DESC, "D3792:XEND:Cryostat ch1 value" ) field (DTYP, "devFromArray") field (INP, "$(SYSTEM):D3640-D4599 @ 152" ) field (SCAN,"$(SCAN) second")

}

となっており、CCL17まではch135までが使われていることが判る。CCL18,19の16チャンネルが抜けているので、CCL18のch001,002,002は レジスタアドレスがD3776,D3777,D3778に対応する。JGW-T1503712中のドキュメント10 p121を見ると、「CENTER_予備 A/D Ch9 仮数部」となっており、予備であることが確認できる。 故に、チャンネルを登録することは簡単で、dbディレクトリに、上記レジスタを持ったレコードを書いてやれば良い。

cry_comp.dbに record (ai, "$(SYSTEM):Comp:Ch8") {

  • field (DESC, "D3775:Compressor ch8 value" ) field (DTYP, "devFromArray") field (INP, "$(SYSTEM):D3640-D4599 @ 135" ) field (SCAN,"$(SCAN) second")

} record (ai, "K1:PEM-BLAB_KIKI_BARO") {

  • field (DESC, "D3776:Barometer value" ) field (DTYP, "devFromArray") field (INP, "$(SYSTEM):D3640-D4599 @ 136" ) field (SCAN,"$(SCAN) second")

} record (ai, "K1:PEM-BLAB_KIKI_TEMP") {

  • field (DESC, "D3777:Thermometer value" ) field (DTYP, "devFromArray") field (INP, "$(SYSTEM):D3640-D4599 @ 137" ) field (SCAN,"$(SCAN) second")

} record (ai, "K1:PEM-BLAB_KIKI_HUMI") {

  • field (DESC, "D3778:Hygrometer value" ) field (DTYP, "devFromArray") field (INP, "$(SYSTEM):D3640-D4599 @ 138" ) field (SCAN,"$(SCAN) second")

}

のように加えた後、IOCを立ち上げ直したが、反映されていない模様。 可能性としては、/home/kagra以下のdbに入れたから?/home/controls以下のdbに入れたから?2つはシンボリックリンクだが、反映されないことがある。←チェックする必要あり。