381
Comment:
|
5245
|
Deletions are marked like this. | Additions are marked like this. |
Line 1: | Line 1: |
Test page | How to realize X arm GR/IR alignment(from IMMT2(SR3) to ETMXY) |
Line 3: | Line 3: |
'''Enter Alignment Mode1''' | |
Line 5: | Line 4: |
* Go to [[http://172.16.32.60/kagra_mannual/img/commissioning_doc.png|Commissioning.Doc]]. * Select "LSC_Lock" in Commissioning.Doc. * Select "request [All]" in [[http://172.16.32.60/kagra_mannual/img/gurad-LSC_LOCK.MAIN.png|LSC_Lock]]. * Select "DOWN" in [[http://172.16.32.60/kagra_mannual/img/gurad-LSC_LOCK.STATES.png|All]]. |
1. '''Enter Alignment Mode1''' * Go to [[http://172.16.32.60/kagra_mannual/img/commissioning_doc.png|Commissioning.Doc]]. * Select "LSC_Lock" in Commissioning.Doc. * Select "request [All]" in [[http://172.16.32.60/kagra_mannual/img/gurad-LSC_LOCK.MAIN.png|LSC_Lock]]. * Select "DOWN" in [[http://172.16.32.60/kagra_mannual/img/gurad-LSC_LOCK.STATES.png|All]]. * '''Enter Alignment Mode2''' * Go to [[http://172.16.32.60/kagra_mannual/img/commissioning_doc.png|Commissioning.Doc]]. * Select "SEMI AUTO ALIGNMENT" in Commissioning.Doc. * Select "! engage" in [[http://172.16.32.60/kagra_mannual/img/salignment.png|SEMI AUTO ALIGNMENT]]. * ''' X arm GR alignment (ITMY misalign).''' * Go to [[http://172.16.32.60/kagra_mannual/img/guardian_overview.png|Guardian Overview]]. * Select "VIS_ITMY" in Guardian Overview. * Select "request [All]" in [[http://172.16.32.60/kagra_mannual/img/guard-VIS_ITMY_MAIN.png|VIS_ITMY]]. * Select "Misaligned" in [[http://172.16.32.60/kagra_mannual/img/guard-VIS_ITMY_STATES.png|All]]. * ''' X arm GR alignment (Resonate GR).''' * Go to [[http://172.16.32.60/kagra_mannual/img/guardian_overview.png|Guardian Overview]]. * Select "XARM" in Guardian Overview. * Select "request [All]" in [[http://172.16.32.60/kagra_mannual/img//GRD-XARM_MAIN.png|XARM]]. * Select "Misaligned" in [[http://172.16.32.60/kagra_mannual/img/GRD-XARM_STATES.png|All]]. * You can see [[http://172.16.32.60/kagra_mannual/img/AOS-TMSX_GR_PDA1_OUTPUT.png|K1:AOS-TMSX_GR_PDA1_OUTPUT]] enhancement. * ''' X arm GR alignment (Check spot position).''' * Go to [[http://172.16.32.60/kagra_mannual/img/commissioning_doc.png|Commissioning.Doc]]. * Select CAMERA. * Select "TCAM Comm Mode" in [[http://172.16.32.60/kagra_mannual/img/IFO_CAM.png|CAMERA]]. * Select "X_end_TCAM Commissioning mode start in [[http://172.16.32.60/kagra_mannual/img/CAL_TCAM.png|TCAM Comm Mode]]". * access [[http://172.16.33.39/vacuum|http://172.16.33.39/vacuum]] for ETMX Spot Monitoring. * access "! Tcam IX" for ITMX Spot Monitoring in [[http://172.16.32.60/kagra_mannual/img/IFO_CAM.png|CAMERA]]. * ''' X arm GR alignment (PR3 Dithering).''' * Go to [[http://172.16.32.60/kagra_mannual/img/guardian_overview.png|Guardian Overview]]. * Select "XARM" in Guardian Overview. * Select "request [All]" in [[http://172.16.32.60/kagra_mannual/img/GRD-XARM_MAIN.png|XARM]]. * Select "MANUAL", then "ENGAGE_PR3_ADS" in [[http://172.16.32.60/kagra_mannual/img/GRD-XARM_STATES.png|All]]. * ''' X arm GR alignment (find good FP axis & PR3 P/Y).''' * Go to [[http://172.16.32.60/kagra_mannual/img/commissioning_doc.png|Commissioning.Doc]]. * Select "ALL VIS" in Commissioning.Doc. * Select "CRY-P" for both ITMX and ETMX in [[http://172.16.32.60/kagra_mannual/img/VIS_ALL.png|ALL VIS]]. * Select "OL SETPOINT" for ITMX and ETMX in [[http://172.16.32.60/kagra_mannual/img/CRY_CUST_TYPEA_OVERVIEW.png|CRY-P]]. * You can find for both ITMX and ETMX. Right click on [[http://172.16.32.60/kagra_mannual/img/CRY_CUST_TYPEA_MN_OLSET.png|slide bar]] and select “-1” as an increment. Never select large increment. * Adjust (IE)TMX alignment to lead their spots on both (IE)TMX to be around center. Ideally, K1:AOS-TMSX_GR_PDA1_OUTPUT should be maximized. *Or, Maximize K1:AOS-TMSX_GR_PDA1_OUTPUT by adjusting, firstly Yaw of IETMX and secondly Pitch. 1 Remember the value of K1:AOS-TMSX_GR_PDA1_OUTPUT (assuming VtmsxGR-0). 2 Anyway, move Yaw/ETMX in one direction until you observe slight reduction of VtmsxGR-0. 3 Move Yaw/ITMX in both direction to find max of VtmsxGR. (4-1) If you can find better VtmsxGR than Vtmsxgr-0, it means your selection for ETMX actuation is good direction. (4-2) If worse, bad direction. 5 If good, repeat (2) (3) until you encounter (4-2). If bad, select opposite actuation then repeat (2)(3) until you encounter (4-2) again. 6 If you find max point, perform (1)~(5) for Pitch/(IE)TMX. (1)~(6) is regarded as one “set” optimization.Ideally, it is better to perform 2 sets for each Yaw/Pitch. * ''' X arm FP axis is established and PR3 P/Y is fixed.''' * '''X arm GR alignment (Record good TMSX).''' * '''X arm IR alignment (Resonate IR).''' * '''X arm IR alignment (PR2-IMMT2 alignment).''' * '''X arm IR alignment (GR/IR resonance check).''' * '''X arm GR/IR alignment Established.''' * '''Y arm IR alignment Preparation.''' * '''Y arm IR alignment (Resonate IR).''' * '''Y arm IR alignment (Check spot position on ETMY).''' * '''Y arm IR align (Adjust BS for ETMY spot centering).''' * '''Y arm IR alignment (ITMY,ETMY alignment).''' * '''Y arm IR alignment (Check spot on ITMY).''' * '''Y arm IR alignment Established.''' * '''Y arm IR alignment (Record good TMSY).''' * '''Y arm IR alignment Established.''' * '''Y arm GR alignment (Resonate GR).''' * '''Y arm GR alignment (TMSY GR maximize with SR3).''' * '''Y arm GR/IR alignment Established.''' * '''FPMI Recovery (Exit from alignment mode).''' * '''FPMI Recovery (Align ITMX).''' * '''FPMI Recovery (Start FPMI).''' |
How to realize X arm GR/IR alignment(from IMMT2(SR3) to ETMXY)
Enter Alignment Mode1
Go to Commissioning.Doc.
- Select "LSC_Lock" in Commissioning.Doc.
Select "request [All]" in LSC_Lock.
Select "DOWN" in All.
Enter Alignment Mode2
Go to Commissioning.Doc.
- Select "SEMI AUTO ALIGNMENT" in Commissioning.Doc.
Select "! engage" in SEMI AUTO ALIGNMENT.
X arm GR alignment (ITMY misalign).
Go to Guardian Overview.
- Select "VIS_ITMY" in Guardian Overview.
Select "request [All]" in VIS_ITMY.
Select "Misaligned" in All.
X arm GR alignment (Resonate GR).
Go to Guardian Overview.
- Select "XARM" in Guardian Overview.
Select "request [All]" in XARM.
Select "Misaligned" in All.
You can see K1:AOS-TMSX_GR_PDA1_OUTPUT enhancement.
X arm GR alignment (Check spot position).
Go to Commissioning.Doc.
- Select CAMERA.
Select "TCAM Comm Mode" in CAMERA.
Select "X_end_TCAM Commissioning mode start in TCAM Comm Mode".
access http://172.16.33.39/vacuum for ETMX Spot Monitoring.
access "! Tcam IX" for ITMX Spot Monitoring in CAMERA.
X arm GR alignment (PR3 Dithering).
Go to Guardian Overview.
- Select "XARM" in Guardian Overview.
Select "request [All]" in XARM.
Select "MANUAL", then "ENGAGE_PR3_ADS" in All.
X arm GR alignment (find good FP axis & PR3 P/Y).
Go to Commissioning.Doc.
- Select "ALL VIS" in Commissioning.Doc.
Select "CRY-P" for both ITMX and ETMX in ALL VIS.
Select "OL SETPOINT" for ITMX and ETMX in CRY-P.
You can find for both ITMX and ETMX. Right click on slide bar and select “-1” as an increment.
Never select large increment.
- Adjust (IE)TMX alignment to lead their spots on both (IE)TMX to be around center. Ideally, K1:AOS-TMSX_GR_PDA1_OUTPUT should be maximized.
- Or, Maximize K1:AOS-TMSX_GR_PDA1_OUTPUT by adjusting, firstly Yaw of IETMX and secondly Pitch.
- 1 Remember the value of K1:AOS-TMSX_GR_PDA1_OUTPUT (assuming VtmsxGR-0). 2 Anyway, move Yaw/ETMX in one direction until you observe slight reduction of VtmsxGR-0. 3 Move Yaw/ITMX in both direction to find max of VtmsxGR. (4-1) If you can find better VtmsxGR than Vtmsxgr-0, it means your selection for ETMX actuation is good direction. (4-2) If worse, bad direction. 5 If good, repeat (2) (3) until you encounter (4-2). If bad, select opposite actuation then repeat (2)(3) until you encounter (4-2) again. 6 If you find max point, perform (1)~(5) for Pitch/(IE)TMX. (1)~(6) is regarded as one “set” optimization.Ideally, it is better to perform 2 sets for each Yaw/Pitch.
X arm FP axis is established and PR3 P/Y is fixed.
X arm GR alignment (Record good TMSX).
X arm IR alignment (Resonate IR).
X arm IR alignment (PR2-IMMT2 alignment).
X arm IR alignment (GR/IR resonance check).
X arm GR/IR alignment Established.
Y arm IR alignment Preparation.
Y arm IR alignment (Resonate IR).
Y arm IR alignment (Check spot position on ETMY).
Y arm IR align (Adjust BS for ETMY spot centering).
Y arm IR alignment (ITMY,ETMY alignment).
Y arm IR alignment (Check spot on ITMY).
Y arm IR alignment Established.
Y arm IR alignment (Record good TMSY).
Y arm IR alignment Established.
Y arm GR alignment (Resonate GR).
Y arm GR alignment (TMSY GR maximize with SR3).
Y arm GR/IR alignment Established.
FPMI Recovery (Exit from alignment mode).
FPMI Recovery (Align ITMX).
FPMI Recovery (Start FPMI).