Line 9: Line 9:
|| 3|| Vacuum tanks (center room) ||<)> 1 kW || ×24h×365×100% ||<)> 8,760 kWh || || 3|| Vacuum pump               ||<)> 1 kW || ×24h×365×100% ||<)> 8,760 kWh ||

変電設備

配電盤

年間電力使用量試算 by Kuroda

1

Compressor for cryocooler 1

264 kW

×24h×365×100%

2,312,640 kWh

2

Vacuum pump

50 kW

×24h×365× 5%

21,900 kWh

3

Vacuum pump

1 kW

×24h×365×100%

8,760 kWh

4

Air conditioner w/ HEPA

10 kW

×12h×365×100%

43,800 kWh

5

Computer w/ air conditioner

80 kW

×24h×365×100%

700,800 kWh

6

Measurement instruments

5 kW

×12h×365×100%

21,900 kWh

7

Lighting equipment

2 kW

×24h×365× 20%

3,504 kWh

8

Cooling water pump  

1 kW

×24h×365×100%

8,760 kWh

Total sum.      

413 kW

 3,122,064 kWh