Size: 1904
Comment:
|
Size: 2071
Comment:
|
Deletions are marked like this. | Additions are marked like this. |
Line 3: | Line 3: |
== 1. Open sitemap on an workstation == | == DC status on each mode's GDS_TP screen should be 0x0. == === 1. Open sitemap on an workstation === |
Line 10: | Line 12: |
== 2. Open CDS screen == |
=== 2. Open CDS screen === |
Line 16: | Line 17: |
== 3. Open GDS_TP screen of each model (blue buttons) == | === 3. Open GDS_TP screen of each model (blue buttons) === |
Line 18: | Line 19: |
== 4. Check that "DC Status" is 0x0 == | === 4. Check that "DC Status" is 0x0 === |
Line 24: | Line 25: |
|| x4000|| It is OK. Data is being sent and you can leave it. A master IOP gets this error when the timing synchronization is fucked up. || || x2000|| It is OK. When the master IOP's timing is not synchronized properly, their slave models show this code.|| |
|| x4000|| It is OK. Data is being sent and you can leave it. There is some synchronization error. || || x2000|| It is OK. Data is being sent and you can leave it. There is some synchronization error.|| |
Line 29: | Line 30: |
(1) When DC status is 0x2 | === (1) When DC status is 0x2bad === |
Line 36: | Line 37: |
(2) When DC status is blank 1. First, make sure the model's channel list is registered in {{{master}}}. |
=== (2) When DC status is blank === ==== 1. First check ==== make sure the model's channel list is registered in {{{master}}}. |
Line 46: | Line 48: |
are written in the file. If they are, but still blank, then | are written in the file. ==== 2. If master is ok, but still blank, or, if you changed master file ==== |
Line 56: | Line 60: |
If even this did not work, try to reboot the data concentrator: | ==== 3. If neither above did not work ==== Reboot the data concentrator: |
Line 61: | Line 66: |
==== 4. Rebooting did not work ==== Call Osamu or Keiko. |
Check if the real time models are sending data to DAQ
DC status on each mode's GDS_TP screen should be 0x0.
1. Open sitemap on an workstation
$sc $medm sitemap.adl
2. Open CDS screen
3. Open GDS_TP screen of each model (blue buttons)
4. Check that "DC Status" is 0x0
DC status |
What to do |
0x0 |
Good status! |
x4000 |
It is OK. Data is being sent and you can leave it. There is some synchronization error. |
x2000 |
It is OK. Data is being sent and you can leave it. There is some synchronization error. |
0x2bad |
Bad. The real time model is not sending data to the data concentrator machine, k1dc0. Go to (1) |
blank |
Bad. Channels are not registered to send to k1dc0. Go to (2) |
(1) When DC status is 0x2bad
ssh <FE macehine name such as k1pr0> sudo /etc/init.d/mx_stream restart
mx_stream process will automatically start up again, and the DAC status will be cleared.
(2) When DC status is blank
1. First check
make sure the model's channel list is registered in master.
t cd fb emacs master
Check if
- tpchn_modelname.par
- MODELNAME.ini
are written in the file.
2. If master is ok, but still blank, or, if you changed master file
ssh k1dc0 ps -ef | grep daqd
Check the process number of daqd. There may be two or three and pick the first and left number (###).
kill ###
daqd process will automatically start up again, and the DAC status will be cleared.
3. If neither above did not work
Reboot the data concentrator:
ssh k1dc0 sudo reboot
Wait patiently until k1dc0 restarts.
4. Rebooting did not work
Call Osamu or Keiko.