Size: 605
Comment:
|
← Revision 19 as of 2016-03-25 09:31:33 ⇥
Size: 1922
Comment:
|
Deletions are marked like this. | Additions are marked like this. |
Line 3: | Line 3: |
1. Open sitemap on an workstation | == DC status on each mode's GDS_TP screen should be 0x0. == === 1. Open sitemap on an workstation === |
Line 8: | Line 10: |
Line 11: | Line 12: |
1. Open CDS screen [[attachment:sitemap.png|{{attachment:sitemap.png|text describing image|width=300}}]] 1. Open GDS_TP screen of each model (blue buttons) |
=== 2. Open CDS screen === |
Line 21: | Line 16: |
=== 3. Open GDS_TP screen of each model (blue buttons) === | |
Line 22: | Line 19: |
1. Check that "DC Status" is 0x0 | === 4. Check that "DC Status" is 0x0 === |
Line 25: | Line 22: |
|| DC status || What to do || || 0x0 || Good status! || || x4000|| It is OK. Data is being sent and you can leave it. There is some synchronization error. || || x2000|| It is OK. Data is being sent and you can leave it. There is some synchronization error.|| || 0x2bad || Bad. The real time model is not sending data to the data concentrator machine, k1dc0. Go to (1) || || blank || Bad. Channels are not registered to send to k1dc0. Go to (2) || === When DC status is blank === ==== 1. First check ==== make sure the model's channel list is registered in {{{master}}}. {{{ t cd fb emacs master }}} Check if 1. tpchn_modelname.par 1. MODELNAME.ini are written in the file. ==== 2. If master is ok, but still blank, or, if you changed master file ==== ''' Before doing this, let everyone know that DQ will be killed ''' {{{ ssh k1dc0 ps -ef | grep daqd }}} Check the process number of daqd. There may be two or three and pick the first and left number (###). {{{ kill ###}}} {{{daqd}}} process will automatically start up again, and the DAC status will be cleared. ==== 3. If neither above did not work ==== Reboot the data concentrator: {{{ ssh k1dc0 sudo reboot}}} Wait patiently until {{{k1dc0}}} restarts. ==== 4. Rebooting did not work ==== Call Osamu or Keiko. |
Check if the real time models are sending data to DAQ
DC status on each mode's GDS_TP screen should be 0x0.
1. Open sitemap on an workstation
$sc $medm sitemap.adl
2. Open CDS screen
3. Open GDS_TP screen of each model (blue buttons)
4. Check that "DC Status" is 0x0
DC status |
What to do |
0x0 |
Good status! |
x4000 |
It is OK. Data is being sent and you can leave it. There is some synchronization error. |
x2000 |
It is OK. Data is being sent and you can leave it. There is some synchronization error. |
0x2bad |
Bad. The real time model is not sending data to the data concentrator machine, k1dc0. Go to (1) |
blank |
Bad. Channels are not registered to send to k1dc0. Go to (2) |
When DC status is blank
1. First check
make sure the model's channel list is registered in master.
t cd fb emacs master
Check if
- tpchn_modelname.par
- MODELNAME.ini
are written in the file.
2. If master is ok, but still blank, or, if you changed master file
Before doing this, let everyone know that DQ will be killed
ssh k1dc0 ps -ef | grep daqd
Check the process number of daqd. There may be two or three and pick the first and left number (###).
kill ###
daqd process will automatically start up again, and the DAC status will be cleared.
3. If neither above did not work
Reboot the data concentrator:
ssh k1dc0 sudo reboot
Wait patiently until k1dc0 restarts.
4. Rebooting did not work
Call Osamu or Keiko.