Differences between revisions 5 and 101 (spanning 96 versions)
Revision 5 as of 2019-12-13 09:06:45
Size: 5088
Editor: guiguo.ge
Comment:
Revision 101 as of 2019-12-17 15:18:02
Size: 4847
Comment:
Deletions are marked like this. Additions are marked like this.
Line 1: Line 1:
= For collaborator shifts =
Line 2: Line 4:
 * Collaboration shift routine tasks
  *
  *
  *
 * When FPMI cannot keep lock state for over 10 minutes or cannot got to lock state ---> call operation shift members.
 * Operator shift table in [[https://gwdoc.icrr.u-tokyo.ac.jp/cgi-bin/private/DocDB/ShowDocument?docid=10914|JGW-M1910914]]
 * Some information for collaborator shifts in [[https://gwdoc.icrr.u-tokyo.ac.jp/cgi-bin/private/DocDB/ShowDocument?docid=9380|JGW-M1809380]]

----
== Collaboration shift routine tasks ==

 1. Write "Log book" ([[https://gwdoc.icrr.u-tokyo.ac.jp/cgi-bin/private/DocDB/ShowDocument?docid=11124|JGW-E1911124]]) on the desk in the control room.
  * Put check mark every 2 hours.
  * Write down everything you noticed.
   * Example: lock lost, earthquake, somebody entered mine etc.
 * When FPMI cannot keep lock state for over 10 minutes or cannot got to lock state
  ---> call operation shift members
   * contact person on the day is listed with '''PHONE NUMBER''' around white board in the control room or see the link [[https://gwdoc.icrr.u-tokyo.ac.jp/cgi-bin/private/DocDB/ShowDocument?docid=10914|JGW-M1910914]] (no phone number in this list)
 * Please write [[http://klog.icrr.u-tokyo.ac.jp/osl/|klog]]: [[http://klog.icrr.u-tokyo.ac.jp/osl/]] before you leave control room.
  * Writing [[http://klog.icrr.u-tokyo.ac.jp/osl/|klog]] is very important. This is only one tool which can show the status in the control room to outside.
  * Account name and password are shown on the white board in the control room.
 * Leave message on "Takeover note" ([[https://gwdoc.icrr.u-tokyo.ac.jp/cgi-bin/private/DocDB/ShowDocument?docid=5032|JGW-T1605032]]) on the desk in the control room if you have something to tell to the next shift.
 * Improve this wiki page if you had something you did not understand well and you found what it is.
  1. Search "KAGRA wiki" in google and access to KAGRA top page.
  * Go to ERun top page on the second line of KAGRA Top page, and go to "Collaborator shift manuals". That page is this manual.
  * Login KAGRA wiki, and press "Edit" button around the top left.
   * Account name and password are shown on the white board in the control room.
Line 9: Line 28:
 . <<TableOfContents(2)>> ------
  
Line 12: Line 32:
 . {{attachment:image1.jpeg||width="1000"}}  * IFO Monitor: shows the status of the Main Interferometer
 . {{attachment:IFO1.png||width="630"}}
 * CCD Monitor:
 . {{attachment:CCD.jpg||height="881"}}
 * DAQ/VIS status:
 . {{attachment:vis status.png||height="681"}}
 * PEM Monitor: Room temperature/ Vacuum pressure
 . {{attachment:Pem.jpg||width="630"}}
 * Time: show JST/UTC/GPS time
 . {{attachment:GPS t ime.jpg||width="430"}}
Line 14: Line 43:
 . {{attachment:IMG_4929.jpg||width="430"}}
Line 16: Line 44:
== How to use Guardian == ----
= How to check Guardian =
[[http://gwwiki.icrr.u-tokyo.ac.jp/JGWwiki/KAGRA/Commissioning/Phase1/Operation/ShiftManual#How_to_reset_Watch_Dogs|how to use Guardian]]
Line 18: Line 48:
 . On the desktop, you can click the sitemap.

 . {{attachment:112.png||width="630"}}
Line 19: Line 52:
 {{attachment:sitemap_guardian.png||height="172",width="430"}} <<BR>> It pops up the following screen, <<BR>> {{attachment:guardian_howto3.png||height="281",width="434"}}
 . {{attachment:116.png||width="730"}}
. Meaning of the background color
. {{attachment:guardian_explanation.png||width=""}}
Line 27: Line 61:
== How to know the status of the interferometer ==
 . Look at one of the TV monitor in the control room. If "ON", it is in OPERATION mode.
 {{attachment:obs_state.png||height="233",width="465"}} <<BR>>If "OFF", check the guardian overview screen<<BR>> {{attachment:guardian_howto3.png||height="281",width="434"}} <<BR>>Check the state of LSC_MICH. First check if the request state of LSC_MICH is OPERATION. If it is not, request OPERATION.<<BR>> {{attachment:guardian_howto4.png||height="281",width="434"}}
 . If the state is ''READY, ENGAGE_SERVO, ENGAGE_BOOST, MICH_LOCKED, CALIBRATION_INJECTION'', or ''ACTUATORCAL_INJECTION'', the interferometer is now on the way to be OPERATION state. It will be ready soon. <<BR>> /!\ ''' If it does not enter OPERATION state in a few mins. Call the interferometer experts.'''<<BR>> Check the status of ''IMC_LOCK, VIS_BS, VIS_PR2, VIS_PR3''. (Note that ''VIS_PRM'' is not used for now, so just ignore it) <<BR>>For IMC_LOCK, every thing should be green and IMC should be back automatically. <<BR>> {{attachment:IMC_guardian.png||height="293",width="453"}} <<BR>> For example, this is how the IMC_LOCK guardian should normally look like.<<BR>> {{attachment:IMC_guardian_status.png||height="281",width="407"}} <<BR>> /!\ '''If it does not come back in ~ 10 mins, call interferometer/IOO experts.'''<<BR>> For VIS_PR2 and VIS_BS, the state should be ALIGNED. If inot, a notification "please reset Watch Dog!" will show up, and the state is in TRIPPED. In that case, go to the next section to know how to reset Watch Dog. <<BR>> For VIS_PR3, the state should be DAMPED. If it is not, a notification "please reset Watch Dog!" will show up, and the state is in TRIPPED. In that case, go to the next section to know how to reset Watch Dog.
= Check list of the interferometer =
=== Check if the LSC_LOCK Guardian at OBSERVATION state ===
{{attachment:LCSLOCK.png||height="",width="880"}}
Line 32: Line 65:
== How to reset Watch Dogs ==
 0. Request LSC_MICH to be READY by Guardian.
=== Check if all of VIS Guardians are at ALIGNED state ===
Look at Guardian Overview
 {{attachment:VIS guardian.png||height="",width="880"}}
 
OR you can see the VIS status on the Monitor
 {{attachment:VIS guardian 2.png||height="",width="680"}}
 * If the Guardian is at TRIPPED state, you should [[http://gwwiki.icrr.u-tokyo.ac.jp/JGWwiki/KAGRA/Commissioning/Phase1/Operation/ShiftManual#How_to_reset_Watch_Dogs|reset Watch Dogs (WDs)]], OR call operation shift members (contact person TBD).
Line 35: Line 73:
 0. Open Sitemap (from Terminal, type "mk" and press return). === Check the IO Guardian ===
{{attachment:IO guardian.png||height="",width="680"}}
Line 37: Line 76:
 0. Click VIS IO Guardian should at PROVIDING_STABLE_LIGHT state, if not call operation shift members '''ASAP!!!'''(contact person TBD).
Line 39: Line 78:
 0. Click the suspension of which you want to reset Watch Dog
 {{attachment:VISALL.png||width="407"}} <<BR>>
=== Check the Green Laser status ===
 * See if the shutter is on or not. If the background color is green, the shutter is ok/open (red means the shutter is closed).
Line 42: Line 81:
 0. Go to PRs case or BS case {{attachment:shutter.png||height="",width="680"}}
Line 44: Line 83:
=== PRs case ===
 4. Request SAFE by Guardian
Line 47: Line 84:
 4. Open "DETAILS" at bottom right,
 {{attachment:PRTOP.png||width="300"}} <<BR>>
  . and you will find PRs overview screen
 {{attachment:PR.png||width="800"}} <<BR>>
 * see if K1: ALS-X (Y)_ARM_INPUT_OUT is more than 0.7
Line 52: Line 86:
 4. Click WATCHDOG
  . If something is red, press here to reset.
 {{attachment:PRWD.png||width="400"}} <<BR>>
{{attachment:0.7.png||height="",width="680"}}
Line 56: Line 88:
 4. Click DACKILL (see the picture above, PRs overview sceen)
  . If it is not green, press reset.
 {{attachment:DACKILL.png||width="200"}} <<BR>>
 * Check if ALS_PLLX/ALS_PLLY Guardian is at PLL_LOCK state
Line 60: Line 90:
 4. Click Coil Driver WD (picture above, PRs overview sceen) Check if everything is green. If there are red signs, push corresponding WD Pulse ON button and then OFF button
 {{attachment:PR_CDWD.png||width="800"}} <<BR>>

 4. Request DAMPED. For PR2, ~ 10 seconds after the state becomes DAMPED, request ALIENED.

 4. ~ 10 seconds after the suspension gets in a nominal state, request LSC_MICH to be OPERATION.

=== BS case ===
 4. Request SAFE by Guardian

 4. Open "Payload" at bottom center,
 {{attachment:BSTOP.png||width="250"}} <<BR>>
  . and you will find BS payload overview screen
 {{attachment:BSpayload.png||width="800"}} <<BR>>

 4. Click WATCHDOG If something is red, press here to reset.
 {{attachment:PRWD.png||width="400"}} <<BR>>

 4. Click DACKILL (see the picture above for BS overview screen) If it is not green, press reset.
 {{attachment:DACKILL.png||width="200"}} <<BR>>

 4. Click Coil Driver WD (see the picture above for BS overview screen) Check if everything is green. If there are red signs, push corresponding WD Pulse ON button and then OFF button
 {{attachment:PR_CDWD.png||width="800"}} <<BR>>

 4. Request DAMPED. For PR2, ~ 10 seconds after the state becomes DAMPED, request ALIENED.

 4. ~ 10 seconds after the suspension gets in a nominal state, request LSC_MICH to be OPERATION.
{{attachment:PLLXY1.png||height="",width="880"}}

For collaborator shifts


Collaboration shift routine tasks

  1. Write "Log book" (JGW-E1911124) on the desk in the control room.

    • Put check mark every 2 hours.
    • Write down everything you noticed.
      • Example: lock lost, earthquake, somebody entered mine etc.
  2. When FPMI cannot keep lock state for over 10 minutes or cannot got to lock state
    • ---> call operation shift members

      • contact person on the day is listed with PHONE NUMBER around white board in the control room or see the link JGW-M1910914 (no phone number in this list)

  3. Please write klog: http://klog.icrr.u-tokyo.ac.jp/osl/ before you leave control room.

    • Writing klog is very important. This is only one tool which can show the status in the control room to outside.

    • Account name and password are shown on the white board in the control room.
  4. Leave message on "Takeover note" (JGW-T1605032) on the desk in the control room if you have something to tell to the next shift.

  5. Improve this wiki page if you had something you did not understand well and you found what it is.
    1. Search "KAGRA wiki" in google and access to KAGRA top page.
    2. Go to ERun top page on the second line of KAGRA Top page, and go to "Collaborator shift manuals". That page is this manual.
    3. Login KAGRA wiki, and press "Edit" button around the top left.
      • Account name and password are shown on the white board in the control room.


Control Room Overview

  • IFO Monitor: shows the status of the Main Interferometer
  • IFO1.png

  • CCD Monitor:
  • CCD.jpg

  • DAQ/VIS status:
  • vis status.png

  • PEM Monitor: Room temperature/ Vacuum pressure
  • Pem.jpg

  • Time: show JST/UTC/GPS time
  • GPS t ime.jpg


How to check Guardian

how to use Guardian

Accessing to the guardian screen

  • On the desktop, you can click the sitemap.
  • 112.png

  • In the sitemap, you can click on the link for the guardian overview screen.
  • 116.png

  • Meaning of the background color
  • guardian_explanation.png

Knowing the current state and requested state

  • guardian_howto4.png

How to request a state

  • Click on the gray bar in the middle.
    guardian_howto.png
    Then, choose the desired state.
    guardian_howto2.png

Check list of the interferometer

Check if the LSC_LOCK Guardian at OBSERVATION state

LCSLOCK.png

Check if all of VIS Guardians are at ALIGNED state

Look at Guardian Overview

  • VIS guardian.png

OR you can see the VIS status on the Monitor

  • VIS guardian 2.png

  • If the Guardian is at TRIPPED state, you should reset Watch Dogs (WDs), OR call operation shift members (contact person TBD).

Check the IO Guardian

IO guardian.png

IO Guardian should at PROVIDING_STABLE_LIGHT state, if not call operation shift members ASAP!!!(contact person TBD).

Check the Green Laser status

  • See if the shutter is on or not. If the background color is green, the shutter is ok/open (red means the shutter is closed).

shutter.png

  • see if K1: ALS-X (Y)_ARM_INPUT_OUT is more than 0.7

0.7.png

  • Check if ALS_PLLX/ALS_PLLY Guardian is at PLL_LOCK state

PLLXY1.png

KAGRA/EngineeringRun/ER191217_24/Shift (last edited 2020-04-07 12:03:16 by OsamuMiyakawa)